Powder Fire Fighting Project STR

  • Added: 29.09.2012
  • Size: 232 KB
  • Downloads: 1
Find out how to download this material

Description

drawings, PP

Project's Content

icon
icon
icon 75-11-06 АПТ.bak
icon ПЗ.doc
icon 75-11-06 АПТ.dwg
icon Спецификация OPПТ.xls

Additional information

Contents

General part

Operation of the installation

Equipment placement

Calculation of the installation

Power supply

Electrical wiring

Security arrangements

maintenance of the installation

Drawings of AUS grade, APT:

General Data

Fire Alarm Network Wiring Plan

Fire Warning Network Wiring Plan

Control and signalling network wiring plan

Connection Diagram

Cable log

General part

The technical solutions adopted in the project comply with the requirements of environmental, sanitary, fire and other applicable norms and rules, and ensure safe operation of the facility for life and health of people, subject to the measures provided by the project.

The design of automatic fire alarm and fire warning units was carried out under an agreement concluded with OJSC "Special Automatics Plant"

This part of the project has been completed within the scope of SNB 2.02.0504 "Fire Automation" and provides for:

- automatic and remote start-up of the plant;

- shutdown of automatic start-up in case of presence of people in the protected room;

- output of command pulses for shutdown of ventilation systems and activation of warning in case of fire;

- fire alarm, plant actuation and condition of its main components;

- grounding of electrical equipment of the unit.

The requirements of the following regulatory and technical documents are taken into account:

The following normative documents were used in the development of the project:

SNB 1.03.0296 "Composition, procedure for development and approval of design documentation in construction";

SNB 2.02.0201 "Evacuation of people from buildings and structures in case of fire"

PUE "Electrical Installation Rules," sixth edition;

SNB 2.02.0504 "Fire automation";

NPB 152004 "Field of application of fire alarm systems and fire extinguishing systems"

GOST 30331.395 (MEK.36444192) "Electrical installations of buildings. Part 4. Safety requirements. Protection against electric shock. "

Operation of the installation

Selection of automatic fire alarm system (AFS) hardware was made on the basis of analysis of structural and construction characteristics and purpose of premises, taking into account the requirements of the technical specification, regulatory and guidance documents, tactical and technical characteristics and cost of equipment.

The fire alarm at the facility is organized on the basis of the PPKOP "Berezina UKA 12.5/1 PS. "

Fire occurrence in protected rooms is recorded using automatic smoke fire detectors IP 2125M, heat fire detectors IP 10503/2. Manual AC05 fire detectors are installed on the escape routes at an altitude of 1.5 m from the floor level.

When the fire detector is activated, the PPKP device generates a signal "Fire," the light and sound alarm is turned on, notifying of the fire and the need to evacuate from the protected premises.

The installation of powder fire extinguishing protects the premises of the car repair workshop. In the protected room, a method of extinguishing over the entire area is provided.

The powder fire extinguishing system is made with the use of the control and acceptance fire department and control "Berezina UKA 12.5/1 isp. 24 AT "and modules of powder fire extinguishing" Hurricane 1. " At the entrance to the protected room, light annunciators "Do not enter" are installed, inside the room - annunciators "Leave powder" (the annunciator must be visible from any point in the room), and the remote start button of the RMP. Sensors are installed on the entrance doors to turn off the automation.

Module of powder fire extinguishing "Uragan1" contains housing with capacity of 6 l, in which fire extinguishing powder and source of cold gas with electric igniter and aerator for powder fluidisation are located. In the lower part of the housing there is a device with a safety release valve and a powder sprayer. In the upper part, the module is equipped with a bracket and a bracket for attachment to the ceiling floor.

The module is triggered by an electric pulse supplied to the outputs of the electric igniter, in the source of cold gas, intensive gas release begins, leading to an increase in pressure inside the housing, opening the valve and ejecting fire extinguishing powder into the burning zone

Control and control of fire alarm and powder fire extinguishing systems is carried out by means of "Berezina UKP 10/18 PS4" control panel installed in the passageway.

The project provides dry contacts for connection of the transponder of the Discount monitoring system.

According to SNB 2.02.021, a fire warning system with automatic and manual launch of the SO-2 type is provided at the facility.

Equipment placement

Fire alarm detectors are installed in protected rooms on floors at a distance of not more than 9 m from each other - IP2125M; not more than 4 m. - IP 10503/2, manual detectors AC05 are installed on the wall, at a height of 1.5 m from the floor at the evacuation exits.

Instruments "UKA 12.5/1 PS, "" UKA 12.5/1 24 AT, "" Tango PU/ZK, "power supply of IRPA 124 isp. BP to be installed in the office.

Install "UKP 10/18 PS4," "Tango PU/BP8" devices in the pass-through. Place the installation during installation.

Powder fire extinguishing modules "Uragan 1" are installed in the car repair workshop on the floor at elev. + 4.100.

At the entrance to the premises protected by the fire extinguishing unit, light "Do not enter" annunciators are installed, inside the premises - "Leave powder" annunciators (the annunciator must be visible from any point in the room), and the remote start button of the UDP. Sensors are installed on the entrance doors to turn off the automation.

Installation of the fire extinguishing plant shall be carried out in accordance with the design documentation, industry and departmental standards, requirements of technical documentation of the manufacturers of equipment and devices, and on the basis of the project of work performed by the installation organization .

Electrical wiring

Fire detector loops are laid along walls and ceilings in the duct and opened with KSVV cable.

Distance from PS loops to power lines must be not less than 0.5 m.

Fire warning network is performed by PVA wire 2x1.0.

Power supply is provided by IWG cable

Alarm and control networks of the powder fire extinguishing unit

are performed by 2x1.0. PVC wire.

The communication line between XT1 box in a checkpoint and a box of XT2 is carried out by the customer.

Drawings content

icon 75-11-06 АПТ.dwg

75-11-06 АПТ.dwg