Fire Alarm and Warning Project

  • Added: 17.04.2012
  • Size: 773 KB
  • Downloads: 0
Find out how to download this material

Description

Complete set of drawings and documentation.

Project's Content

icon
icon перинат. 5 этаж.dwg
icon перинат. подвал.dwg
icon спецификация перинат.doc
icon структурная перинат.doc
icon перинат. 1 этаж.dwg
icon перинат. 2 этаж.dwg
icon перинат. 3 этаж.dwg
icon перинат. 4 этаж.dwg
icon общие данные перинат.doc

Additional information

General Data

This project is based on the following regulatory and technical documents:

GOST 2799088 Means of security, fire and fire alarm. General technical requirements;

RD 78.VO.0199 Technical means of security systems of objects. Conditionally graphic designations of system elements;

Electrical Installation Rules (PUE);

RD 78.14593 Systems and complexes of security, fire and fire alarm. Rules for production and acceptance of works;

SNiP 110195 Instruction on composition, procedure for development, approval and approval of design and estimate documentation of enterprises;

RD 78.36.0032002 Engineering and technical strengthening. Security equipment. Requirements and design standards for the protection of facilities from criminal encroachments.

VNP-001-01 "Buildings of institutions of the Central Bank of the Russian Federation";

"List of private security equipment authorized for use in 2004."

Characteristics of the protected building

The building of the perinatal building is a 5-story building with a basement. The building has three entrances to the basement. There are eight entrances on the ground floor. On each floor there are two entrances from the elevator block.

Purpose of the system

The fire alarm system is designed for timely notification of the security service about penetration (attempted entry) into the building, fire, and subsequent transmission of signals to the PSC.

Alerting system

The warning system is designed to alert employees and visitors about the fire with the supply of light indicators, sound signals and voice information about the need for evacuation, escape routes and actions aimed at ensuring safety.

The equipment of the foreign company Veelez was chosen for design. Use Veelez warning equipment complex to build the warning system.

The system includes:

expansion and monitoring unit;

a digital message source;

remote microphone console;

power amplifiers (5 pieces 300PP016M and 1 piece 200PP016M);

5AS100FW acoustic systems (loudspeakers);

signs of escape routes;

linear part of the system cable, wires.

The bank warning system is made according to the third type of EPSS .

As a light warning, "Exit" light indicators are selected, which are installed at the stairs, at the entrance to the elevator halls, at the exits from the building.

By means of voice warning, equip places of permanent or temporary accumulation of people.

Place loudspeakers indoors in places where the alert will provide the greatest audibility.

Translation of recorded messages is performed in automatic mode from PPK signals or in manual mode by zones. Each floor is a separate area.

Wall sounders shall normally be mounted at a height of at least 2.3 m from the floor level, but the distance from the ceiling to the sounder shall be at least 150 mm.

Installation works

Wiring of fire alarm loops is performed by 2x0.5 TRP wire, wiring of security alarm loops is performed by 4x0.2 KSPVG cable from instruments to expanders, and from expanders to C2000 panel by UTP 5 cable. Line routing for signals transmission from the station to the annunciators shall be performed using 2x1,2 copper RPPPM wire. Route the wires secretly in the electrical conduit.

Install light and sound annunciators in the security room and near the premises where "Nota1" PPKOP and "Signal VK405" PPKOP are installed.

All detectors, distributions are sealed (sealed).

Drawings content