Object: Bakery and confectionery production. Project developer: PKO LLC'IK Energogarant '. Year of project release: 2011. Systems: Alarm, Fire Alarm

Project's Content

icon
icon
icon
icon Задание - 1Э.dwg
icon Задание - 2Э.dwg
icon Пояснительная записка.doc
icon Проект.dwg
icon Спецификация - лист 1.doc
icon Спецификация - лист 2.doc
icon Спецификация - лист 3.doc
icon Титул - Рабочая проект.doc

Additional information

Contents

1. General part

2. Brief description of the object

3. Main Design Solutions

3.1. Automatic fire alarm

3.2. Fire Warning System

4. Occupational safety

1. Common part.

1.1. This project "Automatic fire alarm and fire warning system" was developed by PKO LLC IK Energogarant in Kstovo on the basis of the design task and contract No. ________________ concluded with the management of LLC "," Moscow.

1.2. The initial design data was the drawings issued by the customer.

1.3. The project is developed in accordance with the requirements of:

Construction Norms and Regulations 110195 "The instruction about an order of development, coordination, a statement and structure of the project documentation on construction of the enterprises, buildings and constructions";

SP 5.13130.2009 "Fire protection systems. Fire alarm and fire extinguishing units are automatic. Design Codes and Regulations ";

SP 3.13130.2009 "Fire protection systems. Warning and management system for evacuation of people in case of fire. Fire safety requirements ";

SNiP 31032001 "Production Buildings";

SNiP 2110185 "Warehouse Buildings";

SNiP 2.09.0487 "Administrative and household buildings";

SNiP 2.08.0289 * "Public buildings and structures";

PUE "Rules for the device of electrical installations" Edition 7.

1.5. The technical solutions adopted in the project comply with the requirements of environmental, sanitary, fire and other standards applicable in the territory of the Russian Federation, and ensure safe operation of the facility for life and health of people, subject to the measures provided by the project.

1.6. The project used equipment that is mass-produced and has certificates of conformity in the GOST R Certification System of the Russian Federation.

1.7. Installation of fire alarm units shall be performed in accordance with VSN 2509.67-85 "Rules of Work Execution and Acceptance. Automatic Fire Extinguishing Units "and RD 78.14593" Guidance Document. Systems and complexes of security, fire and fire alarm. Rules for production and acceptance of works. "

2. Brief description of the object.

2.1. Type of construction - reconstruction.

2.2. The building of LLC "" is a two-story brick building with a basement. The fire resistance degree of the building belongs to category B.

2.3. The building has a flour warehouse and a PIIa flour screening room.

3. Main design solutions.

3.1. Automatic fire alarm.

3.1.1. Taking into account the requirements of the above regulatory documents, the architectural and construction solutions selected a fire alarm system built on the basis of the equipment of the Russian-made NVP Bolid, which has a certificate of conformity and a certificate of fire safety.

3.1.2. All rooms and corridors of the building are equipped with automatic fire alarm, with the exception of bathrooms, washing rooms, pump rooms, refrigeration rooms and other rooms with wet processes, as well as staircases and other technical rooms where there are no burnt materials. Smoke fire detectors of IPD3.1M type are installed in the above rooms.

IP1022x2 detectors designed to detect the rate of temperature rise in the environment are designed in the storage and screening rooms of flour, as well as in the furnace shops. The sectional unit outputs acoustic and light alarms, as well as duplicates the signal "fire" to the device "20M."

Automatic fire detectors are installed on the floor of protected rooms or suspended on a cable. On the escape routes, manual fire detectors of the "IPR3SU" type are installed to provide an alarm when a fire is visually detected.

3.1.3. The following are designed as receiving and control equipment:

- "Signal20M" safety and fire control device;

- sectional unit (BS), for detector IP 1022x2.

Information on the fire, work and malfunctions of the automatic fire alarm is submitted on indicators of the face of the Signal20M device. Messages are recognized by alarm loops and differ in the color of light emitting diodes and their flashing intensity. All elements of the system are in constant diagnostic mode and any deviations from the norm are displayed accordingly.

3.1.4. Fire alarm system generates signals:

for disconnection of systems and devices in case of fire (ventilation, process equipment);

activation of the fire warning system for people; - generation of the "Fire" signal to the local bodies of "State Supervision ."

3.1.5. The wiring is made by a non-spreading cable laid in the cable - channels, corrugated PVC pipes and metal pipes through the intercoupling ceilings.

3.1.6. In standby mode, Signal20M monitors the serviceability of detectors and alarm loops. If loops with fire detectors are damaged, a fault signal is output.

3.1.7. In case of fire, smoke or temperature rise in the guarded room smoke or heat fire detectors are activated. In case of fire detectors actuation, the control and receiving device generates acoustic and light alarms indicating the loop number in which the activated detector is included.

3.2. Warning and management system for evacuation of people in case of fire.

3.2.1. The fire evacuation warning and control system is one of the components of the complex of technical means and organizational measures that ensure the safety of people in case of fire or other emergency.

The fire warning system is designed to inform people about the fire and control their evacuation to a safe area.

3.2.2. In accordance with SP 3.13130.2009, a type 2 warning system was designed at the facility. EPSS of this type ensures the transmission of light and sound message to premises where people can be exposed to a dangerous fire factor, as well as to premises where people can remain when blocking escape routes by fire.

3.2.3. Fire light warning includes "Exit" light indicators installed near evacuation exits. In some places difficult to evacuate, direction boards are installed. LUX NBO TL24 light annunciators are installed at the facility, and Mayak243M type annunciators are designed as sound annunciators. Control, control of lines with annunciators for break and short circuit is built on the basis of the switching device UKVK and diode bridge.

The power and number of audible annunciators is selected based on the requirements to provide a sound level exceeding the level of constant noise by 15 dBA, but not more than 120 dBA at any point in the protected premises.

3.2.4. The sound warning is activated automatically after receiving a fire message using the fire alarm equipment..

The annunciators are always on.

3.2.5. Control of the notification and evacuation process, as well as communication with all responsible persons and services providing control over the fire situation at the facility, is carried out from the premises of the security post. The dispatcher has the highest priority on the influence of EPSS, therefore, a dispatcher with special training is allowed to work with the installation.

3.2.6. To ensure the safety of people, elements of electrical equipment of fire protection plants must meet the requirements of GOST 12.2.007.0. All metal parts of electrical equipment that are not normally energized, but which may be under it, due to failure of insulation, are subject to grounding (earthing). The potentials must be balanced.

Protective grounding (grounding) must be performed in accordance with the "Electrical Installations Design Rules" (PUE, Edition 7, Chapter 1.7), SNiP 3.05.0685 "Electrical Devices," the requirements of GOST 12.1.03081 and the technical documentation of the plants. The resistance of the grounding device shall be not more than 4 ohms and shall be provided by the customer .

4. Occupational safety.

4.1. Compliance with safety precautions is a prerequisite for safe operation during construction, installation and operation of fire extinguishing and fire alarm units.

Violation of safety rules can lead to accidents.

4.2. During installation, maintenance and operation of the plants, the "Rules for operation of electrical installations of consumers," "Safety rules for operation of electrical installations of consumers" of the Software TRM0162001, RD 15334.0-03.15000 "Intersectoral rules for labor protection (safety rules) during operation of electrical installations" must be complied with.

4.3. The installation of the plant should be guided by the requirements of chapter SNiP III48, including the requirements set out in the sections:

- electrical installation works;

- electric welding and gas-flame works;

- Loading and unloading works;

- operation of technological equipment and tools;

- installation works ;

- equipment test.

4.4. When performing electrical installation works, it is also necessary to comply with the requirements of SNiP 3.05.0685 and PUE.

When working with the construction and installation pistol PC 521, it is necessary to comply with the requirements "Instructions for the use of powder tools in the performance of installation and special construction work" VSN 41080. When working with the power tool, it is necessary to comply with the requirements of GOST 12.2.00775. 4.5. During operation of fire alarm units it is necessary to follow the operating manual, technical descriptions and certificates of the equipment included in the unit, RD 25 96490 "System for maintenance and repair of automatic fire extinguishing, smoke removal, safety, fire and fire alarm units, organization and procedure of works," "Rules for technical operation of electrical installations of consumers," "Safety rules for operation of electrical installations of consumers" (PTE and PTE). 4.6. Persons who have undergone a medical examination, who have a document certifying the right to work with the installations and who have received safety training and instruction at the workplace in safe working methods are allowed to service the installations.

4.7. Perform all repair and scheduled works with electrical equipment only after power supply disconnection. The presence of working and protective grounding must be checked.

4.8. See section 6 of the Explanatory Note, Volume I for Occupational Safety for Installation of Automatic Powder Fire Extinguishing Units.