Automatic installation of powder fire extinguishing of garage complex
- Added: 03.08.2014
- Size: 3 MB
- Downloads: 0
Description
Project's Content
|
|
|
|
Общие данные.dwg
|
Пояснительная записка.doc
|
Чертежи.dwg
|
Additional information
Contents
General provisions
Characteristics of the protected object
Main technical solutions adopted in the project
3.1. Purpose of automatic control and control system
3.2. Composition of ATCP
3.3 Purpose and operation principle of APCP and CO unit
3.4. Purpose and characteristics of the equipment used
3.5. Device design and operation
3.6. Use of device by purpose
3.7. Technical Solutions for Location of Used APCP and CO Plant Equipment
WFP (H) -6-I-GE-U2 "Tungus" powder fire extinguishing module
Fire detectors and annunciators
Installation of automatic fire alarm unit
Warning system and EMSS evacuation control
Equipment Placement Solutions
Power supply, grounding and lightning protection
Environmental protection
Fire fighting measures
Safety precautions
Professional and qualification composition of persons working at the facility for maintenance and operation of automatic fire alarm
Operation and maintenance
Typical Maintenance Schedule for APCP
1. general provisions
This working project contains a design solution for the organization of an automatic installation of powder fire extinguishing and an alarm and evacuation system in the premises of a multi-storey garage - parking, which takes into account the requirements of the relevant regulatory documents.
The project was developed in accordance with the Design Code, the requirements of NPB 882001, the rules for the installation of electrical installations (PUE issue 7) with compliance with safety measures according to SNIII480, as well as taking into account architectural planning solutions issued by the Customer on the basis of the Contract, architectural and construction drawings, the MHBTI technical passport of the object and in accordance with the requirements of fire safety standards and rules.
2. characteristic of the protected object.
The facility is located in JSC Moscow .
The parking garage building is a separate, combined, multi-story, with one double-track ramp.
Purpose - permanent storage of passenger vehicles of citizens with provision of minimum service services.
Main architectural and building characteristics of the building:
The vertical volume of the building is divided into 3 above ground floors and 2 ground floors (basement and basement).
The total area of protected premises according to the project is 11972.5 m2,
In the 3-story underground part, box storage for 152 parking spaces was designed.
Entry, exit to the ramp is carried out from Panfilovsky Prospekt.
In the basement and basement, a box storage for 89 cars was designed.
All floors are combined with standard stair runs.
In accordance with SniP, the above-ground and underground compartments are completely isolated from each other by an overlap with a fire resistance of 2.5 hours.
The wash and viewing boxes are located in the basement. To evacuate people there are two staircases. Part of the premises are occupied by the GSK administration:
on the 2nd floor - management room 45 m2;
on the 3rd floor - GSK office 45m2.
Brick building with inner frame of column pitch 7.2x6.6 m and 7.2x 6.0 m.
The width of the driveways is 6.2 m. The entrance-exit ramp is monolithic.
The masonry of the walls is made of brick with facing with red front ceramic brick.
In accordance with SNiP 210299 * p. 5.40, the partitions of the boxes are made of silicate bricks of grade 150, the thickness of the partition is 120 mm and have a fire resistance rating of R 45, fire hazard class K0. Door blocks on escape routes and technical rooms are wooden roofed with galvanized roofing steel on asbestos or felt. The gates of the boxes are metal, at a height of 1.4-1.6m they have holes measuring 300x300 mm to supply extinguishing means and monitor the fire condition of the box. The gate of the wash and viewing boxes is with a wicket and glass in the upper zone. The bindings of windows and stained glass windows are metal, with an opening. Glazing is single.
Functional fire hazard class - F5.2. Degree of fire resistance - II.
Explosion and fire hazard category - B.
In the building there are no rooms of category A on explosive and fire hazard as per NPB10503.
In addition, in accordance with the requirements of SNiP 2.04.0185 "Internal water supply and sewers of buildings," buildings are equipped with fire water supply with a network of fire cranes.
In order to increase the level of fire protection of premises and extinguish possible combustion centers at the facility, primary fire extinguishers are also used.
The class of possible fire in these rooms of the garage complex is B1 (burning of liquid substances insoluble in water (gasoline, petroleum products).
3. main technical decisions adopted in the project.
3.1 Purpose of the automatic powder fire extinguishing unit.
Based on the characteristics of the building, the type of fire load and the features of the development of the combustion center, the design provides for the protection of the room using an automatic fire alarm and fire extinguishing system. It is designed for automatic detection of a fire hazard situation, generation of fire hazard signals, output of information on the presence and location of a fire hazard situation, local activation of powder fire extinguishing modules, supply of a fire warning signal to people and an automatic control signal.
The projected AUPP is constructed on the basis of PPKOP of "ZONDSI" and the complex of the technical means consisting from includes itself: the control panel (further PKU), the device reception and control "PROBE-SI" (further PPKOP), the SS (MShS8) modules on 8 directions, the relay MP8 modules on 8 directions, turning on of modules of powder fire extinguishing of Tungus6, the uninterrupted power supply, smoke fire announcers, thermal fire announcers and tame fire announcers.
In accordance with SNiP 210299 * p. 6.32, for timely notification of people, the project provides for the design of a warning system and the evacuation control of EPSS of the 3rd type on the basis of the "Orpheus" voice warning unit.
For the purpose of early detection of fire, all floors of the building are equipped with automatic fire control systems, regardless of their purpose, with the provision of round-the-clock operation of fire detectors, except for rooms with wet processes (bathrooms, washes, staircases). In all protected storage boxes of cars, detectors are designed that respond to an increase in ambient temperature.
3.2 Composition of the automatic powder fire extinguishing unit.
The APCP system includes:
- fire and security alarm and powder fire extinguishing devices "ZONDSI";
- signal loop module MSHS8;
- relay module MP8;
- uninterrupted DC power supply source BBP20;
- smoke fire detectors IP2donbass 1M (Upit. = 7.0... 30V; Ipot.dezh. = 0.05ma);
- thermal fire detectors IP1034/1 "MC-1" with normally closed contacts (Tsrab. = 64... 76 ° С; Icomut. = 150 mA; Ucomut. = 30.0V);
- manual fire detectors IPR5132 "Agat" (Upit. = 9... 28V; Ipot.dezh. = 0.1ma);
- KOP20 light indicators (Upit. = 10... 40V; Ipotr. St. = 20ma);
- "Orpheus" BRO voice warning unit for translation of pre-recorded voice messages in fire alarm systems.
- Orpheus MA isp.1 sound annunciators - acoustic wall module.
All used equipment and cables have a fire safety certificate.
3.3. Purpose and operation principle of APCP and CO unit.
Automatic installation of powder fire extinguishing is designed to detect the source of fire (fire) when temperature rises and smoke occurs in the premises of the building and to output the corresponding information to the panel of the SondSI PPKOP control and reception device to the duty room located on the ground floor.
In the event of a fire in the protected premises of the garage complex, heat or smoke fire detectors are triggered. Also, a fire signal may be received when the manual fire detector is activated.
Signal on detector actuation is transmitted via wired lines of signalling loop to MSS8 module serving eight signalling loops (SBS), and then via cable to panel of receiving and monitoring floor-by-floor devices "SondSI" installed in the duty room on the 1st floor with round-the-clock stay of duty personnel.
Panel of PPKOP "SondSI" receiving and control device provides actuation of fire warning system through relay on power supply module (MP), provides disconnection of supply and exhaust ventilation and actuates Tungus-6 powder fire extinguishing module in the corresponding direction.
Each MSHS8 module has two relay outlets, one of which controls the ventilation fire valve (from the smoke protection system) installed on the floor where the MSHS8 module is installed. Actuation of these systems is carried out when the detector in the loop is activated twice, which is accordingly provided by the installation programming.
Based on the characteristics of the rooms equipped with automatic fire alarm, the type of fire load and the use of substances and materials, the fire hazard category of the rooms, the design provides for the protection of machine boxes and all other rooms (offices, utility rooms, locker rooms, etc.) with thermal and smoke detectors, which are an effective means for detecting the fire center.
On the escape routes on each floor near the staircases or directly at the exits from the floor, manual fire detectors of the IPR 5132 type are installed at a height of 1.5 meters from the floor level.
The area controlled by one fire detector, as well as the maximum distance between the detectors, as well as the detector and the wall, comply with the requirements of NPB 882001 * "Fire extinguishing and alarm installations. Design Codes and Regulations. "
In accordance with the requirements of NPB 10403 "Warning and Evacuation Systems for Fires in Buildings and Structures," in the corridors of each floor of the garage complex building, a sound and light warning system for people in case of type 3 fire is provided. The number of alerts, their arrangement and power provide the necessary audibility in all places of possible stay of people.
The fire warning system is activated when the automatic fire alarm is triggered. At the same time, sound annunciators are activated on all floors of the building when fire detectors are triggered or a manual fire detector is activated. Electrical evacuation indicators "Exit" are installed on the escape routes according to the design of electrical lighting of the building, which, according to the requirements of paragraph 3.13 of NPB 10403, are in the ON state together with the main lighting devices of working lighting.
3.6. Use of device by purpose
Operational limitations
The design and installation of the instrument shall take into account the following:
- when placing MP8 in remote places of the object, the active resistance of the power supply wires of the modules should be taken into account, since the power required to switch on one relay, 0, 4W at the internal resistance of its winding (300 ± 50) Ohm, and when switching on a large number of relays, the total current can cause voltage drops on the wires that do not allow the relay to switch on;
- it is not recommended to jointly include passive and current-consuming detectors in one SB according to the scheme with the formation of the warning "Attention" (parallel connection of resistor 7.5 kOhm to normally closed contacts of the passive detector and serial connection of the recommended resistor to the current-consuming detector);
- instrument control panel provides software support for exchange with no more than 20 modules connected to the ICR;
- ICS and SB wires shall be laid at a distance of not less than 0.5 meters from any power cables with a voltage of more than 100V or flowing current of more than 1A.
Specifying safety measures
During operation of the device, it is necessary to comply with the rules set forth in the instructions "Rules for technical operation of electrical installations of consumers," "Safety rules for operation of electrical installations of consumers."
The source of dangerous voltage is the supplied power supply voltage
220B. When operating under dangerous voltage, there are MAINS terminals with connected wires, fuses and connecting circuits on the power supply module (MP).
Before connecting the power supply wires, it is necessary to ground the device housing (LB4) and make sure that the connected wires 220V are de-energized.
The modules shall be installed or replaced when the power supply voltage is off.
3.7. Technical solutions for placement of used equipment
APCP and CO units, installation of detectors and loops
Placement of control equipment, detectors, alarm loops and their installation is carried out in accordance with the requirements of NPB 882001 * "Fire extinguishing and alarm units. Design Standards and Rules, "technical and operational documentation for the equipment used, passports, manuals, specifications and other documents.
The SondSI PPKOP devices, which receive all information, are located in the duty room on the 1st floor of the garage complex, where the duty personnel are located around the clock, monitoring the condition of the AUPP installation and taking measures when it is triggered in accordance with the developed and approved instructions.
Said equipment is attached to the wall at a height convenient for maintenance at a height of 0.81.5 m from the floor level. The duty personnel room has natural lighting, as well as artificial lighting of at least 150 lux .
In addition to working lighting, emergency lighting is provided. The room shall be equipped with city telephone communication with the fire department.
Installation of instruments is carried out in a cabinet fixed on the wall taking into account the convenience of operation and maintenance. The MShS8, MRT8 modules placed in cases of LB1 are installed on each floor. Placement of instruments shall prevent their accidental fall or movement along the installation surface, in which the connected wires and cables may be damaged. When placing instruments it is necessary to ensure normal illumination of instrument panels.
Installation of automatic fire alarm loops in protected rooms and along routes is carried out along walls, ceilings and behind the structure of suspended ceilings in a corrugated hose or decorative box. At the points where the cable passes through the holes in the walls, the cable is also protected by corrugating.
In accordance with the requirements of NPB 882001 * "Fire fighting and alarm systems. Design Standards and Rules "automatic fire alarm loops shall be implemented by cables with copper residential diameter of 0.5 mm. The cable type is specified in the specification for the equipment used as part of the detailed design. The area controlled by one fire detector, as well as the maximum distance between the detectors, as well as the detector and the wall, corresponds to the tables specified in NPB 882001 * "Fire extinguishing and alarm installations. Design Codes and Regulations. "