Working drawings of heating networks.
The heat carrier is network water with a temperature of 95-70°C.
The total length of the designed networks is 70 m.
The heat supply system is closed, two-pipe, the regulation of heat energy supply depending on the outside temperature is carried out in the boiler room (high-quality regulation).
The laying of the heating network is adopted above ground on low and high supports.
Connection to the existing heating network ∅159x4.5 is provided in the heat chamber. Turns of the heating network are used as compensators.
At the lowest points of the pipelines, drains are installed, at the upper points - air vents.
Type of fixed supports - frontal two-thrust according to series 4.903-10 issue 4,
movable - sliding supports according to series 4.903-10 issue 5.
Pipeline material - longitudinal electric-welded steel pipes according to GOST 10704-91* made of carbon steel grade St20.
Project's Content
План теплосети.dwg
|
Схема УТ.dwg
|
О.д.Профиль..dwg
|