• RU
  • icon Waiting For Moderation: 0
Menu

Polyclinic in the city of Taganrog. Section OG

  • Added: 01.05.2022
  • Size: 3 MB
  • Downloads: 0
Find out how to download this material

Description

Heating, ventilation and air conditioning in the health centre

Project's Content

icon Текстовая часть ИОС.ОВ (поликлиника ул.Бакинская).docx
icon 1 часть_ОВ_поликлиника.dwg
icon 2 часть_ОВ_поликлиника.dwg

Additional information

Section 5. information on engineering equipment, utilities networks, list of engineering measures, content of technological solutions

SUBSECTION 5.4. HEATING, VENTILATION AND AIR CONDITIONING.

Design documentation - Reconstruction of buildings and structures (KN 61:58:0004487:69; KN 61:58:0004487:67; KN 61:58:0004487:68) in the clinic at the address: ul. Baku, 56; Taganrog; Rostov region is developed on the basis of:

- engineering specification;

- tasks of adjacent sections;

- SP 60.13330.2012 "Heating, ventilation and air conditioning";

- SP 131.13330.2012 "Construction climatology";

- SP 50.13330.2012 "Thermal protection of buildings";

5.4.1. Information on climatic and meteorological conditions of the construction area, design parameters of outdoor air.

Design ambient temperatures:

- design temperature for heating design - 18 ° C

- design temperatures for ventilation systems design

in cold period -18 ° C

in warm period + 27 ° C

- design temperature for air conditioning design + 32 ° C

- average temperature of heating period 0 ° C

- duration of heating period 165 days.

5.4.2. Information on heat supply sources, coolant parameters of heating and ventilation systems.

The source of heat supply for the needs of heating, heat supply of ventilation systems is the roof boiler room.

The coolant in the heating system is hot water with 8060 ° C.

Coolant in the heat supply system of plenum plants - hot water with parameters of 9570 ° С.

Hot water is supplied to the building by separate pipes from the roof boiler room (see section VK).

Hot water temperature - 65 ° C.

5.4.3. Substantiation of adopted systems and fundamental decisions on heating, ventilation and air conditioning of premises.

Heating

The selection of the heating system and the calculation of the number of heating devices required to heat the entire volume of the building are based on the calculation of heat losses through external enclosing structures (walls, windows, doors, floors, coating).

Hydraulic calculation is performed according to REHAU program .

The results of calculation of heat consumption for the designed building are presented in the table of basic indicators for CW systems.

The heating system is adopted as double-tube, horizontal, with associated movement of the coolant in the main lines .

Bimetallic "BMN" radiators of the company "SANTEKHPROM" are adopted as heating devices. Automatic air valves are installed on all heating devices for air discharge. Automatic temperature controllers TS90V and shutoff valves RL1 of "HERZ" company are installed to control heat removal of heating devices and maintain regulated internal air temperatures in the rooms on the supply lines to the radiators.

Hydraulic adjustment of floor risers of the heating system is provided using automatic balancing valves 4007 from HERZ.

Water is lowered from risers through drain cranes.

Main pipelines of heating systems, risers and supply to instruments are designed from universal pipes RAUTITAN pink and stabil (REHAU, Germany). Pipelines are laid in 9 mm thick Energoflex pipe insulation.

The distance from the bottom of the heating device to the floor level is at least 100 cm.

Compensation of heat extensions of main pipelines of heating systems is provided due to angles of turns, lowering and lifting.

At the intersections of wall and slab pipelines, pipelines shall be laid in sleeves in accordance with SNiP 3.05.0185 "Rules of Work Execution and Acceptance."

Heat supply to plenum plants

The heat supply system of plenum plants is adopted according to the dependent connection scheme. Coolant temperature in the heat supply system is 95-70 ° С.

Pipelines are designed from steel water and gas pipes (GOST 326275) and steel electric welded pipes (GOST 1070491).

Automatic air vents are installed in the upper points of the system to remove air. For emptying - drain cranes are installed in the lower points.

Heat supply system pipelines are heat insulated in the following composition:

- anti-corrosion heat-resistant enamel "Zerta" as per TU 2312001492488462000;

- main insulation layer - URSA GEO M25 mats 20 mm thick (NG)

- cover layer - fiberglass rolled as per TU 22960140020496199 (NG).

To ensure circulation and control of coolant temperature of plenum plants, "NED" mixing units are designed, which are included in the supply set of plenum plants.

Power supply of pumps of heat supply mixing units of plenum plants is accepted according to 1 category.

Ventilation

In the clinic, a supply and supply ventilation system with mechanical and natural motivation is designed.

"NED" plenum units are designed for air inflow.

Air intake for plenum systems is carried out through an external grille installed at a height of 2 m from ground level.

Air is released at a height of not less than 1 m above the roof level.

Separate systems of plenum and exhaust ventilation are designed for the premises of cafes (P6, B18), swimming pool (P5, B16), LFK halls (P3, B10, B12), basement (P2), wards, rooms of each floor (P1, P7, B17, B20, V22, Vrazov, 29, VdY2, 29,

Exhaust ventilation from the premises of the clinic is carried out by channel fans installed behind the set ceiling of the corridors and in the serviced room, as well as roof fans.

Air ducts for general ventilation systems are designed from thin-sheet galvanized steel (GOST 1491880) of class H with a thickness of SNiP.

Transit air ducts are made of thin-sheet galvanized steel according to GOST 1491880, class "P," 1.0 mm thick, EI 60.

Plenum and exhaust systems are equipped with adjustable grilles of the RV type from Roven.

Fire protection valves of KPU1N type with fire resistance limit EI 90, "Veza" company, with Belimo electric drives are provided at the crossings of fire partitions.

All transit air ducts shall be insulated with heat and heat protection coating "ALU1 Wired Mat 80" 40 mm thick.

All supply ducts shall be insulated by self-adhesive foil insulation, 10 mm thick.

Places of passage of transit air ducts through walls, partitions and ceilings are sealed with non-combustible materials, providing a fire resistance limit of the intersected floor.

In the warm period, in order to maintain a comfortable internal air temperature in the cafe and pool premises, plenum systems (P5, P6) are provided with cooling (KKB5, KKB6).

Noise reduction measures

To reduce noise and vibration from supply and exhaust ventilation systems, the project provides for the following set of measures:

- plenum units are located in a separately enclosed soundproofed room;

- plenum plants of NED company, have a framework structure with heat and sound insulation from mineral wool fiber;

- ventilation units are accepted with sections of silencers;

- connection of fans with air ducts is made through flexible inserts;

- air speeds in air ducts and coolant in pipelines are accepted based on the condition of creation of permissible noise level.

5.4.5. Justification of optimum location of ventilation equipment.

Fans of plenum systems P2, P3, P5 are located in the ventilation chamber in the basement of the building at el. 7,050.

Fans of plenum systems P4, P6 behind suspended ceilings.

Fans of plenum systems P1, P7 are located in the ventilation chamber on the 4th floor.

Fans of exhaust systems are installed behind the set ceiling of corridors, in serviced rooms and on the roof of the building.

5.4.6. Description of technical solutions ensuring reliability of systems operation in extreme conditions.

In the premises of the institution, extreme conditions are possible in the event of a fire.

In this case, ventilation systems are automatically switched off.

5.4.7. Description of automation and dispatching systems for heating, ventilation and air conditioning control.

To ensure the reliability of ventilation systems, it is provided:

- automatic disconnection of general ventilation systems;

- automatic closing of fire-fighting "normally open" valves of KPU1N from PPS.

5.4.8. Automation.

The automation project (Section 01.02.302017IOS.AK) of heating and ventilation is developed on the basis of the technical specification of Section II.

The project has adopted showing devices necessary for temperature and pressure control in the heating and hot water supply system. It is accepted to control the temperature of the network water depending on the temperature of the outside air.

Electrical equipment and junction boxes shall be grounded in accordance with applicable PUE standards.

The shield, instruments and automation equipment are supplied complete with "NED" fans.

Drawings content

icon 1 часть_ОВ_поликлиника.dwg

1 часть_ОВ_поликлиника.dwg

icon 2 часть_ОВ_поликлиника.dwg

2 часть_ОВ_поликлиника.dwg
up Up