Sales Rows - AUPS
- Added: 30.08.2014
- Size: 2 MB
- Downloads: 1
Description
Project's Content
|
ПС-ПЗ пояснительная записка.doc
|
ПС_1.dwg
|
СО_cпецификация.doc
|
Additional information
Contents
1. GENERAL INFORMATION
2. FIRE ALARM SYSTEM FACILITY CHARACTERIZATION
3. PURPOSE AND OBJECTIVES OF THE SYSTEM
FIRE ALARM
4. TECHNICAL SOLUTIONS
5. FIRE WARNING SYSTEM FOR PEOPLE
6. FIRE ALARM LOOPS, CABLES AND WIRES
7. FIRE ALARM SYSTEM INTERCONNECTION
WITH OTHER SYSTEMS
8. POWER SUPPLY
9. HEALTH AND SAFETY MEASURES
10. ENVIRONMENTAL PROTECTION
General Information
1.1. Full name of the developed project: "Fire alarm system of the Unysh market on the street. Veresaev Aircraft Building District of Kazan" Further in the text - ATP.
1.2. Regulatory documents
The technical solutions adopted in the project comply with the requirements of the following regulatory documents:
The following documents were used in the design:
- Federal Law N 123FZ "Technical Regulations on Fire Safety Requirements";
- SP 1.13130.2009. Set of rules. Fire protection systems. Escape routes and exits;
- SP 3.13130.2009. Set of rules. Fire protection systems. Fire evacuation warning and control system. Fire safety requirements;
- SP 5.13130.2009. Set of rules. Fire protection systems. Fire alarm and fire extinguishing units are automatic. Design Codes and Regulations;
- SP 6.13130.2009. Set of rules. Fire protection systems. Electrical equipment. Fire safety requirements;
- PPB 0103 "Fire Safety Rules in the Russian Federation";
- RD 0090196 "Fire Automation Units. Technical Content Rules ";
- RD 78.14593 "Guidance document. Systems and complexes of security, fire and fire alarm. Rules of Work Execution and Acceptance ";
- Rules of electrical installations device (PUE);
-SP 12.13130.2009. Set of rules. Determination of categories of rooms, buildings and outdoor installations by explosion and fire hazard.
Characteristics of the fire alarm system object
2.1 Dimensions of the protected room.
2.1.1 Protected rooms:
- Unysh market premises (hereinafter referred to as the market).
2.1.2 Protected area in plan:
- market - 832 m2.
2.1.3 Height of the room at the highest point:
- market - 2.3 m.
2.2 Characteristics of the protected room.
In the protected room there are retail departments specializing in retail.
Purpose and objectives of fire alarm system
3.1. Purpose of the system
The fire alarm system is designed for automatic detection of fire centers when the controlled fire factors exceed the established threshold values in the protected object, automatic fire alarm and timely notification of personnel about the fire.
3.2. Objectives of System Creation
The system is designed to prevent human and material losses and ensure the environmental safety of work.
Technical solutions
The fire alarm system of the building was developed on the basis of equipment from NVP Bolid. The following technical means are provided for the implementation of this system:
light fire annunciator "Lightning 12" ("Exit" annunciator);
"S2000" fire control and monitoring panel
block of indication "S2000BI";
Smoke detector optoelectronic IP 21241M;
Manual fire detector "IPR 5136" (IPR I);
Safety-fire control device "SMD 20P signal."
Standby power supply "BIRP 12/4.0";
Fire smoke detector linear optoelectronic 4-wire IPDLDII/4P.
The automatic fire alarm system is designed for early detection and determination of the fire source address in the controlled rooms, output of "Fire" and "Malfunction" signals to the duty personnel at the permanent duty station.
In the security room, the "S2000" fire control and monitoring panel is installed, designed to work as part of the fire alarm system to monitor the condition and collect information from the system devices. The console combines the devices connected to it into one system, ensuring their interaction with each other. The panel allows displaying on the liquid crystal display (LCD) messages about fires, alarms, malfunctions, security, removal from protection and other events occurring in the system. It is possible to sound alarm messages. The console stores messages in a non-volatile event buffer from which they can be viewed on the LCD. Instruments "C2000," "C2000BI" and "20P SMD signal" are combined into a network via RS485 interface.
Fire detectors shall be installed in all public and service premises to detect the fire source, and manual fire detectors shall be installed on escape routes and at exits. Receiving and control devices are located in the security room.
Installation of fire detectors is also provided for detection of the fire source in the backfill space. To determine the location of the fire detector, they are connected by independent SGs and have remote optical indication. The design of the false ceiling provides access to the service of detectors.
PPKOP "20P SMD signal" allows to adjust parameters of SB and relay operation programs. Control programs must be set to control the relay.
The main components of the system are described below.
4.1 Characteristics of PPKOP "SMD 20P signal":
Number of signaling loops - 20;
Number of control programs for each output - 37;
Internal buffer capacity - 64 events;
Supply voltage - from 10.2 to 28 V;
Current consumption by the device, in standby mode:
at 24 V power supply: from 200 mA to 400 mA
at 12 V power supply: from 300 mA to 600 mA
Loop load current - 3 mA;
Control of 5 relay outputs;
Operating temperature range - from minus 30 to + 50 ° С.
4.2 Characteristics of "C2000" PCMS:
number of devices connected to RS485 interface - up to 127
number of partitions - up to 255
number of signaling loops that can be combined into sections - up to 512
up to 511 user passwords
number of relay outputs controlled in automatic mode - up to 255
event buffer size - 1023 messages
RS485 interface line length - up to 4000 m
RS232 interface line length for communication with printer - up to 20 m
supply voltage - from 10.2 to 28.4 V
keyboard - 16 keys with backlit
indicator - LCD with illumination, 16 characters
operating temperature range - from + 1 to + 40 ° С
4.3 Characteristics of "S2000-BI":
The number of two-color indicators to display the status of sections is 60;
The number of single-color system indicators for displaying received messages is 8;
Supply voltage - from 10.2 to 28.0 V;
Current consumption, in standby mode - 200 mA;
The number of devices connected to the serial interface is 127.
Fire Warning System
For rooms of this type, according to NPB 10403, a fire warning system of the second type is provided. To alert people about the fire, a lightning alert "Lightning 12" ("Exit" annunciator) and a light-sound alert "Mayak12KP" installed on the escape routes are provided. Warning networks are performed by KMVngLS 2x2x0.5 cable. Wires, cables should be laid in a cable channel and corrugated pipe made of self-extinguishing plastic on walls at a distance of at least 10 cm from the ceiling.
For warning in the security room there is a "S2000" fire control and monitoring panel with light and sound indication.
Fire alarm loops, cables and wires
Loops of the fire alarm are executed by independent KMVVngLS cable 1х2х0.5 and KMVVngLS 2х2х0.5 with copper veins. Cables shall be laid in cable channel and corrugated pipe made of self-extinguishing plastic.
Power supply lines are made by independent cables. Joint laying of fire alarm loops and connecting lines, warning units control lines with 110 V and more lines in one conduit, construction structure or on one tray is not allowed.
Joint laying of said lines is allowed in different compartments of boxes and trays having continuous longitudinal partitions with fire resistance rating of 0.25 h from non-combustible material. In case of parallel open laying the distance from wires and fire alarm cables to power and lighting cables shall be not less than 0.5 m.
Interconnection of fire alarm system with other systems
Transmission of "Fire" signal through switching devices is provided with "SMD 20P signal" PPKOP.
Power supply
According to the degree of reliability of power supply, electrical receivers of fire alarm systems are classified as 1 category, and power supply of the plants should be carried out in accordance with PUE.
For backup power supply of all devices of the fire alarm system, 2 BIRP 12/4.0 are provided, containing 2 storage batteries 12 V. 7 Ah.
ПС_1.dwg