Power supply of ADES with capacity of 2190 kW
- Added: 14.11.2014
- Size: 493 KB
- Downloads: 0
Find out how to download this material
Subscribe to receive an information about new materials:
Description
1. Outdoor lighting of the territory; 2. Grounding and lightning protection. To illuminate the perimeter of the territory, cantilever lamps of the RKU type are adopted, with mercury lamps installed on wooden supports. Power supply and control of outdoor lighting is performed from the operator room. The grounding circuit is made of round steel with a diameter of 10 mm into a trench at a depth of at least 0.5 m. All circuits of grounding devices are connected to each other at least at two points. All connections are made by electric welding, except for tanks with fuel, where connections are made only using bolts with nuts and spring washers. For grounding of tanker trucks, at fuel drain, installation of grounding device of VUUK-UZA type is provided. Lightning protection is carried out by lightning receptors installed on rod lightning rods and on wooden lighting supports.. To prevent lightning current from spreading along the outer grounding loop, each lightning connector is connected to the grounding loop through a vertical grounding conductor made of round steel and is installed in the well to a depth of 3 m.
Project's Content
es-ades-sakkyryr.dwg
|
Additional information
Drawings content
es-ades-sakkyryr.dwg
Similar materials
- 24.02.2022
- 08.06.2023
Free downloading for today
Update after: 22 hours 15 minutes
- 24.04.2014