Cinema and extension to the cinema - auto. Fire alarm installation

  • Added: 29.07.2014
  • Size: 394 KB
  • Downloads: 0
Find out how to download this material

Description

Fire alarm and warning system of the cinema based on the equipment of ZAO NVP Bolid

Project's Content

icon
icon
icon Cinema Pioner_APS_1.dwg
icon PZ1.doc
icon Tituli_1.doc
icon Zadaniya_1.doc

Additional information

Contents

1. General part

2. Characteristics of the protected object

3. Purpose of automatic fire alarm

4. Main technical solutions adopted in the project

5. Principle of operation of automatic fire alarm

6. Electrical wiring

7. Grounding

8. Information on the organization of installation works

9. Health and safety measures

1 General part.

A working project for automatic installation of fire protection for the premises of the Pioneer Cinema and the extension to the cinema, located at:

Moscow, developed on the basis of the Agreement and the terms of reference issued by the Customer.

The work project has been completed in accordance with the requirements of:

- NPB 882001 * "Fire fighting and alarm units. Design Codes and Regulations ";

- SNiP 11.0195 "Instruction on the composition, procedure, development, approval and approval of design and estimate documentation for the construction of enterprises, buildings and structures;

- NPB 11003 "List of buildings, structures, premises and equipment to be protected by automatic fire extinguishing units and automatic fire alarm;

- NPB 10403 "Design of fire warning systems for people in buildings and structures";

- RD 78.14593 "Manual to the guidance document of the security, fire and fire alarm system and complex. Rules of Work Execution and Acceptance ";

- PUE, Electrical Installation Rules (Edition 7).

3 Purpose of the installation.

Automatic fire alarm installation is designed to detect fire in protected rooms, to generate a fire signal and information about the plant operation, to start the fire warning system, to control the building engineering equipment.

4 Main technical solutions adopted in the project.

As equipment for automatic fire alarm installation, the project provides for the use of equipment manufactured by the Bolid LDP. The project involves merging, using an interface line

RS-485 of "S2000M" control and monitoring panel and PPKOP "Signal20P SMD" control and monitoring device for monitoring fire alarm loops in rooms installed in the security room. Relay outputs of control and receiving devices and relay amplifier of UKVK type are used for process equipment control.

Relay outputs of the control and receiving device are also used to start the fire warning system for people.

The AUPS equipment shall be installed on the ground floor of the building in the security room. Install on the wall at a height of 1.6 m from the floor elevation.

Install emergency lighting in the security room and provide artificial lighting of at least 150 lux for fluorescent lamps and at least 100 lux for incandescent lamps. Emergency lighting shall provide illumination on working surfaces of at least 10% of the corresponding standards, according to NPB882001 *.

Provide measures preventing access of unauthorized persons to AUPS equipment.

Control panel okhrannopozharny "C2000M"

Intended for use as a part of the system of the security and fire alarm together with reception and control devices "Signal20", "Signal20P", "C20004", "Signal20" series 02, controllers of the two-wire S2000KDL line, devices reception and control and managements of firefighters of "S2000ASPT", relay S2000SP1 blocks, and "S2000KPB", the C2000K and C2000KC keyboards, blocks of indication "S2000BI", controllers of management of access of "C20002".

Basic functions

• Monitoring of up to 127 instruments connected to the console via RS485 interface;

• Display on LCD, store in non-volatile buffer all events occurring in the system and print them to the printer with serial RS232 interface;

• Alarm alarm on built-in audio alarm;

• Control of taking/removing and monitoring of alarm loops condition from the console;

• Programming of device configuration parameters, printing of configuration on printer, setting of device addresses and address devices;

• Restricting access to password management and programming functions;

ADDITIONAL CAPABILITIES

• Case with large LCD display with high information content (2 lines of 16 characters). There are functional LEDs "ALARM," "FIRE," "MALFUNCTION," "ALARM" showing the state of the object;

• The number of sections and signaling loops that can be included in these sections has increased, allowing this console to be used in larger facilities;

• The maximum number of user passwords has increased;

• Sections can be grouped together. This simplifies group management of security placement and removal from security. Any section can be included in multiple groups;

• Ability to specify text names not only for sections and users, but also for section groups and signaling loops. The text name can be up to 16 characters long;

• Ability to change message names from signaling loops. You can specify 32 custom rename scenarios for each signaling loop added to the console database. Each scenario allows you to specify new text names and display type for any 4 standard device signaling loopback messages;

• Configuration of the console is performed by the program "Database Administrator" from AWS "Orion Pro" or by the utility "pprog.exe" version 2.00 and higher.

FUNCTIONS AVAILABLE AFTER CONFIGURATION

• Combining loops into sections;

• Display section text names and user names in the event log. String length - up to 16 characters;

• Control of sections collection/removal and monitoring from "S2000K" panel and keyboards, "S2000KS" panels and "S20004" devices;

• Possibility of management of the outputs of C20004, Signal20P and Signal20 devices series 02. Possibility to control relay outputs with delay;

• Transfer of the events which are taking place in a system to the C2000K keyboards for indication and to informants of "S2000IT" for transfer by subscriber phone line;

• A personal computer with "C2000" AWS software can be connected to the console to maintain the event log and display the states of the sections and signaling loops on the computer;

• The console in programming mode can perform the function of the interface converter "RS232 - RS485," which allows you to configure the console and devices connected to it from a personal computer without using additional interface converters;

• Possibility of connection of several fire alarm subsystems based on "C2000" panels to personal computer with AWS "Orion." Such a system has all the advantages of the Orion AWS and works when the personal computer is turned off;

• Configuration is performed by PPROG.EXE.

PPKOP device "SMD 20P signal" provides:

• Connection of 20 alarm loops with all types of fire detectors

• Programming of loopback parameters for a specific object of operation.

• Increased noise immunity due to selection of input signal by duration and filtering of directives 50 Hz;

• Voltage in each 12V signaling loop;

• Adaptation to loop resistance;

• Having a 2-wire RS485 interface allows you to:

o control state of loops, display messages from loops on "C2000" panel or AWS "Orion";

o to register events on the printer by means of the C2000 remote controller or on the computer (through "P");

o configure loopback parameters;

• Control of operation of one ("Warning") and two ("Fire") fire detectors in the loop and monitoring of failure of the loop ("Fault");

• Serviceability in case of RS485 interface violation and after its restoration, transmission of accumulated messages to C2000 console or Orion AWS with time of their occurrence.

Based on the characteristics of the premises equipped with automatic fire alarm, combustible materials stored in them, and also in accordance with Appendix 12 of NPB 882001 *, the design provides for:

For the purpose of early detection of a fire and delivery of an evacuation signal, the premises are protected by smoke detectors of type IP 21245.

Smoke fire detector optoelectronic two-wire

IP 21245, is designed to detect sunbathing, accompanied by the appearance of low concentration smoke in closed rooms. It is distinguished by its modern design, small dimensions, high sensitivity and noise immunity. It is adapted for operation with any receiving and control fire alarm devices of both Russian and imported production, which provide supply voltage in the alarm loop in the range from 7.5 to 30 V and perceive the "Fire" signal in the form of a jump decrease in the detector internal resistance in direct polarity to a value of not more than 500 Ohm.

Technical specifications:

Sensitivity: 0.05-0.2 dB/m.

Actuation inertia: not more than 5 s.

Current consumption in standby mode: 0.05 mA

Designed for continuous operation at ambient temperature from minus 25 to plus 55 ° С

Overall dimensions of detector with socket: not more than 93 x 60 mm.

Average service life: at least 10 years.

Smoke fire detectors are installed on the ceiling, on the path of the most likely smoke flow.

Each room is protected by at least two fire detectors (item 12.16 of NPB 882001 *).

In accordance with item 13.2 * NPB 882001 *, the circuit for switching on the detectors in the fire alarm system provides for the output of the signal "Fire," when one smoke detector is activated (the second detector is duplicate and serves to increase the reliability of the system in case of failure of one of the detectors installed in the room).

To send a signal about a fire in case of its visual detection by duty or maintenance personnel, it is provided to place manual fire detectors of IPR-I type at the main and spare evacuation exits.

Place the manual detectors according to the working drawings on the wall at a height of 1.5 m from the floor level.

Actuation of the manual detector sets PSK to "Fire" mode, bypassing "Attention" mode.

The choice of fire detectors of this type is justified by the most complete compliance of their parameters with the characteristics of the protected premises, as well as the requirements of NPB 11003.

To alert people about a fire occurring in the premises, a sound warning system of the 2nd type is adopted.

The CO equipment performs the following main functions:

• Ensuring the necessary audibility in all places of permanent or temporary stay of people;

• Light indicators "Exit";

• Preservation of serviceability in the absence of main power supply.

To ensure serviceability of the fire alarm system during 24 hours in standby mode, 3 hours in alarm mode, 1 hour in the mode of operation of the warning system when the main power supply is disconnected, a backup power supply is provided "RIP 12 isp. 05 "complete with a 12 V, 17 A * h battery and a box for additional installation of 1 12 V, 17 A * h battery.

Power supply of "Output" light indicators with built-in backup power source is performed directly from the building power distribution panel.

The equipment envisaged in the design can be replaced with similar equipment in terms of purpose, parameters and properties, in the presence of certificates of conformity and fire safety, valid in the territory

of the Russian Federation.