• RU
  • icon Waiting For Moderation: 16
Menu

Automatic smoke removal of 12th residential building

  • Added: 14.08.2014
  • Size: 1 MB
  • Downloads: 1
Find out how to download this material

Description

The object is a twelve-story residential building.
Height of protected rooms up to 3 m.

Selection of automatic fire alarm system (AFS) hardware was made on the basis of analysis of structural and construction characteristics and purpose of premises, taking into account the requirements of technical specification, regulatory and guidance documents, tactical and technical characteristics and equipment cost.

Project's Content

icon
icon
icon
icon 9392_ADU2.doc
icon 9392АДУ2.dwg
icon 9392АУС.dwg
icon plot.log
icon задание.doc
icon ЗапискаАУС.doc
icon
icon Бланк временных позиций.doc
icon Бланк исх д.xls
icon Бланк исх д1.xls
icon Задание ОАСП на составление СО.doc
icon Общие сведения.doc
icon Титул.doc
icon ТитулАУС.doc

Additional information

General part

The technical solutions adopted in the project comply with the requirements of environmental, sanitary, fire and other applicable norms and rules, and ensure safe operation of the facility for life and health of people, subject to the measures provided by the project.

The project was completed under the contract 9392.02ADU concluded with the State Unitary Enterprise "Housing Repair and Maintenance Association No. 1."

The following regulatory and technical documents were used in the development of the project:

SNB 1.03.0296 "Composition, procedure for development and approval of design documentation in construction";

SNB 2.02.0201 "Evacuation of people from buildings and structures in case of fire"

PUE "Electrical Installation Rules," sixth edition;

SNB 2.02.0504 "Fire automation";

NPB 152004 "Field of application of fire alarm systems and fire extinguishing systems"

GOST 30331.395 (MEK.36444192) "Electrical installations of buildings. Part 4. Safety requirements. Protection against electric shock. "

The initial design data was the approved design assignment and drawings submitted by the customer.

Description and characteristics of the object

The object is a twelve-story residential building.

Height of protected rooms up to 3 m.

The facility is located at: Minsk, 19 Prytytsky St.

Key Technical Solutions

Selection of automatic fire alarm system (AFS) hardware was made on the basis of analysis of structural and construction characteristics and purpose of premises, taking into account requirements of technical specification, regulatory and guidance documents, tactical and technical characteristics and equipment cost.

The fire alarm is organized on the basis of the equipment of the Spectron system, which is installed in the electrical panel.

Control of fire alarm system (setting, removal, release of alarms, etc.) is performed from BI02 indication unit. System status information is output to indication unit BI02.

Fire alarm is made using automatic fire smoke optoelectronic detectors IP 212-5M

According to SNB 2.02.0201, a fire warning system of the SO-1 type is provided at the facility. ASTO12S/1 light-and-sound placards with "Exit" inscription are used as warning devices. The warning system is controlled by Tango control unit.

"Fire" and "Fault" signals are output to control room (refer to design. 9390ADU2).

Equipment placement

During installation of fire alarm system components, refer to references on drawings, certificates and technical descriptions on

equipment and materials used.

The system equipment is mounted in the electrical panel: Tango PU device at an altitude of 0.8-1 .5 m. The BA01 device (see project 9392.02ADU2)

Fire alarm system detectors are installed in corridors (see project 9392.02ADU2) and in the control room.

ASTO 12С/1 light-and-sound placards with "Exit" inscription are installed above evacuation exits at the altitude of 2.3m .

ELECTRICAL WIRING

The fire alarm network shall be wired by KSPV cable in the duct by walls and ceilings.

Light-and-sound indicators of fire warning system are connected

by PVA wire, wire branching is performed through KO-4 boxes.

Power supply of equipment

The fire alarm unit is a category 1 consumer and requires two independent power supplies.

Operating input 220V, 50Hz is supplied to VZ IP power supply.

Calculation of battery capacity for VZ IP power supply.

Security arrangements

PLANT MAINTENANCE

To protect maintenance personnel from dangerous voltages that may occur on electrical equipment housings as a result of insulation damage, grounding of electrical equipment housings is provided. Grounding of electrical equipment shall be performed by metal connection of its housings to neutral of power supply network of objects, for which a separate third, protective conductor, laid together with wires of other purposes, is used. When performing works, follow GOST30331.395 (IEC 36444192)

"Electrical installations of buildings. Part 4. Safety requirements. Protection against electric shock. "

General part

The electrical part of the smoke removal plant design is executed in accordance with the contract concluded with the State Unitary Enterprise "Housing Repair and Maintenance Association No. 1," the design task and is performed in accordance with the current norms and rules and ensures explosion and fire safety of the plant operation in compliance with the measures stipulated by the project .

The following regulatory and technical documents were used in the development of the project:

SNB 1.03.0296 "Composition, procedure for development and approval of design documentation in construction";

SNiP 3.05.0685 "Electrical devices";

SNB 2.02.0504 "Fire automation";

PUE "Electrical Installation Rules," sixth edition;

"Manual on operation and installation of automated fire protection systems in residential buildings of higher storeys."

"Automatic smoke protection systems for high-rise residential buildings." VSN 60-89

GOST 30331.395 (MEK.36444192) "Electrical installations of buildings. Part 4. Safety requirements. Protection against electric shock. "

The initial design data was the approved design assignment and drawings submitted by the customer.

Operation of the installation

The smoke removal plant protects the escape routes of the building in the event of a fire. The prompters for starting the plant are smoke detectors installed in the corridors of a residential building (IP2125M) and button posts installed in the niches of fire cranes.

To automate the smoke removal installation, the project provides for equipment of the Spectron system. Smoke removal system includes alarm and control units of FCS, FCS and BI02 indication unit.

The fire signal is transmitted from smoke fire detectors to the alarm and control unit. The FCS gives the command to open the valves to the relay BR unit. For manual start of smoke removal system there are buttons in fire niches. Button stations connected to BR are used for serviceability check of valves.

At the same time, a command is received to BUSO units for starting of exhaust and plenum ventilation motors. CSCS receive information from power cabinets about their switching on, loss of power phase, switching to manual mode. Command is given to switch elevators to "Fire hazard" mode.

All system status information is transmitted to BI02 indication unit. From BI02 indication unit "Fire" and "Malfunction" signals are transmitted to dispatching personnel panel located in residential building, refer to Pushkin, 32.

Electrical panel room and boxes U996 are equipped with security alarm. In attempt of unauthorized access to the room or to devices the signal is transmitted to the A16512 device (cm project 9390ADU2).

Power supply

The plant is a category 1 power consumer and is powered by two independent sources.

Supply lines ~ 380V after ALT to the engine control cabinets are supplied by the customer according to the task of BelPKI "Special Automatics." VZ power supply is supplied from B1ShK cabinet.

Calculate the battery for the VZ power supply:

Equipment placement

Push-button stations for serviceability check of valves are installed near them at a height of 1.5 m. BSU units, relay units BR02K are installed in the corridor on each floor in U996U3 boxes. Units BI02, BUSO and WCS cabinets are installed in the electrical panel in the basement at a height of 0.81.5 m. The distance between the equipment is not less than 0.05m.

The equipment of the security alarm system - the A602 device is installed in switchboard.

Electrical wiring

The smoke removal signalling network shall be wired along the walls and ceiling with KSPV cable, LWV cord in the duct. Power supply ~ 220V is performed by IWG cable. Power supply from cabinets to motors - by PV1 wire in the pipe. 24V devices are powered by PVC wire. External cable networks are performed by the customer according to the Task of BelPKI "Special Automation"

Security arrangements

PLANT MAINTENANCE

To protect maintenance personnel from dangerous voltages that may occur on electrical equipment housings as a result of insulation damage, the electrical equipment housings are provided for. Electrical equipment must be used by metal connection of its housings to the neutral of the power supply network of the objects, for which a separate one is used

third, protective conductor laid together with wires of other assignments. During works, refer to GOST 30331.395 (IEC 36444192) "Electrical installations of buildings. Part 4. Safety requirements. Protection against electric shock. "

Drawings content

icon 9392АДУ2.dwg

9392АДУ2.dwg

icon 9392АУС.dwg

9392АУС.dwg
up Up