Fire Alarm and Warning System Project for Holy Trinity Church
- Added: 03.08.2014
- Size: 753 KB
- Downloads: 1
Description
Project's Content
|
|
|
|
ПЗ.doc
|
Подключение приборов.vsd
|
Проект.dwg
|
Additional information
Contents
General provisions
2 Description and characteristics of the object
2.1 Characteristics of the protected object
2.2 Characteristics of rooms
3 Basic Technical Solutions
3.1 Organization of fire alarm system
3.1.1 Description of OPS units
3.1.2 Technical data of OPS units
3.2 Fire Warning Organization
3.2.1 Description of warning installations
3.2.2 Technical data of warning units
3.2.2.1 Functional parameters
"TOWER 5200" amplifier
3.2.2.2 Connection of loudspeakers
3.3 Organization of alarm signal transmission to PCP
3.4 System power supply
4 Installation of equipment and wiring
5 Equipment grounding
6 Requirements for installation and operation
7 Basic Safety Rules
General provisions
1.1 The working design of the fire alarm and fire warning system was developed on the basis of the agreement No. of April 8, 2005 and the Customer's task.
1.2 The working design is performed in accordance with the requirements of:
• NPB 882001 "Fire fighting and alarm units. Nor-us and design rules. "
• GOST 12.04.00983 "Fire equipment for protection of objects. General requirements. "
• GOST 21.10197 "SPDS. Basic requirements for design and detailed design documentation. "
• SNiP 110195 "Instruction on the composition, procedure for development, approval and approval of design documentation for the construction of enterprises, buildings and structures."
• SNiP 210197 (1999) "Fire safety of buildings and structures."
• NPB 10896 Religious facilities. Fire protection requirements.
• PUE "Electrical Installation Rules."
• NPB 10495 "Design of warning systems for people about heat in buildings and structures."
2 Description and characteristics of the object
2.1 Characteristics of the protected object
Fire alarm equipment shall be provided for all rooms except the toilet (elev. + 4.200). Equipment with security alarms are subject to: the area of the front side of the iconostasis in the prayer hall, deacon, corridor at elev. + 4.200, external doors along the perimeter of the object.
Internal walls, partitions are made of small cement-sandwiched blocks, floors and arched (semicircular) lintels, the monolithic vault is reinforced concrete. Ceiling floors are prepared for painting, arched openings are plastered along the grid, walls and partitions are plastered. The premises of the narthex, refectory, prayer hall are prepared for painting.
2.2 Characteristics of rooms:
• Category of premises by explosion and fire hazard - B4.
• Relative humidity - up to 70%.
• Ventilation is natural.
• Air temperature - from + 5 С to + 20 С.
3 Basic Technical Solutions
The main control device of the system is PC with installed AWS "Orion" software. 10, read for control of 10 devices ("S2000," "Signal20P," "S2000-4," etc.); at shutdown of network food of PEVM the system passes under management of the C2000 device.
The automatic system of the okhrannopozharny alarm system and the notification about the fire is intended for delivery of signals "Attention", "Fire" and "Malfunction" to personnel on duty to a post of the round-the-clock watch in the building of the temple, for transfer of a disturbing signal on PCN in the system of "Inflow" and formation of an impulse for management of the system of the sound and speech notification about the fire.
3.1 Organization of fire alarm system
3.1.1 Description of OPS units
The following equipment is provided in the design. Equipment of NVP "Bolid" company - address devices: fire safety control and monitoring panel "S2000," receiver-control device "Signal-20P SMD," receiver-control security device "S2000401," repeat RS485 interface with galvanic isolation "S2000PI."
Equipment of the company "System Sensor" - fire detector smoke-electronic "IP 21273" (Profi-O), fire detector thermal maximum-differential "IP 10131 A1R" (Profi-T), fire detector smoke linear "6500R," fire detector manual "WR2061SR" for remote control "KR,"
Equipment of other companies - security volume detector "Photon," security magnetic contact detector "IO1026."
3.1.2 Technical data of OPS units
Orion AWS software is installed on IBM compatible PC and runs Microsoft Windows 2000, Windows NT 4.0, Windows XP. Russified versions of OS data are desirable. Minimum requirements for PCMs: Pentium III 850, 128Mb RAM, SVGA 32Mb, 50GB on HDD, mouse, sound card, recommended monitor screen size from 19 to 21 inches.
The following Orion AWS software subsystems are involved in this project:
• "Operational task" - is intended for logging of events, control of security and removal from security of objects, monitoring and graphical display of the state of sections and zones of the object, voice warning in case of alarm situations.
• "Database Administrator" - is designed to manage the input, editing, sorting and exchange of data necessary for the correct operation of the security system.
• "Report Generator" - is designed to generate reports on the status and events of the hardware part of the integrated system at a user-defined time interval.
• "System Wizard" - designed to archive, restore, delete information entered into the system database.
• "Shleifes" - designed to display the state of loops in real time.
• "Plan Editor" - designed to draw plans of premises of security objects.
• components "Uprog," "Demonstrator" and "Configuration of C2000 console" - are designed to emulate the operation and configuration of devices.
Orion or the C2000 remote controller provides to PEVM with an automated workplace reception of signals, through the addressed devices "C2000", "Signal20P SMD", "C2000401" from automatic and tame announcers.
Simultaneous operation with PC devices with AWS "Orion" and "S2000" bullets is not possible, therefore redundancy is performed by switching over of devices control from PC to "S2000" panel at disconnection of PC. When the PC is restored, the control is rotated by the Orion AWS. For redundancy "C2000" panel operation mode is used, when it acts as RS232 - RS485 interface converter, if PC polls the devices, and if there is no interrogation within the specified time it goes into active state (starts working with the devices). Once the PC device poll is restored, the console returns to interface converter mode. When the console is in interface converter mode, any control of the instruments from this console is not possible. Also in this station, the console does not display information from connected devices, there is no access to the event buffer. When the console enters the active mode, its functions (instrument control, event log viewing, etc.) become available. Events that occurred in the system during operation of the panel with instruments will remain in the buffer of events of this panel and will not be subtracted by AWS "Orion" at restoration of PC operation.
To set the mode of interface converter with automatic switching to active mode in the panel, set the mode of panel operation as per RS232 ("MODE" parameter of "55 RS232" menu) to "PI/RESERVE." Besides, it is necessary to set a delay of transition to the active mode at loss of contact with the computer (BOCCT TIME parameter of the 55 RS232 menu). The delay can be in the range of 1-255 seconds, the recommended value is at least 60 seconds.
The system has an interface line, which is a two-wire communication line of the trunk structure with visual and audible indication of alarm and malfunction on the system devices.
The system generates the signal "Attention" at actuation of one detector in the fire loop and the signal "Fire" at actuation of the second detector in the same loop, as well as the signal "Fault" at short circuit or alarm loop break.
Fire alarm loops are connected to "Signal 20P SMD" device (designation on diagrams - ARK2). Distribution of firefighters:
ShS1 - the left side of the molal hall on otm.+4.200;
ShS2 - a vestry, a dyakonnik on otm.+4.200;
ShS3 - the center of the molal hall on otm.+4.200;
ShS4 - an entrance of the molal hall on otm.+4.200;
ShS5 - the right side of the molal hall on otm.+4.200;
ShS6 - ladder flight, economic. rooms on otm.+4.200;
ShS7 are service premises, a corridor on otm.+4.200;
ShS8 - the molal hall on otm. 0.000;
ShS9 - an antechurch, knot of input, the booth, a refectory on otm. 0.000;
ShS10 - an entrance of the molal hall on otm.+11.200;
ShS11 - the left side of the molal hall on otm.+11.200;
ShS12 - a vestry, a dyakonnik on otm.+11.200;
ShS13 - the right side of the molal hall on otm.+11.200;
ShS14 - the center of the molal hall on otm.+11.200;
ShS15 - the center of the molal hall on otm.+11.200;
ShS16 - ShS20 - a reserve.
Loops of the security alarm system are connected to C2000401 devices (designation on schemes - ARK3, ARK4). Distribution of security SRs:
"C2000-4-01" (designation on schemes - ARK3):
ShS1 - the belfry hatch on otm.+8.200;
ShS2 are external doors from a facade on otm. 0.000;
ShS3 - a corridor on otm.+4.200;
ShS4 - a reserve.
"C2000-4-01" (designation on schemes - ARK4):
ShS1 are external doors left on otm. 0.000;
ShS2 - an iconostasis;
ShS3 are external doors of a dyakonnik, a dyakonnik on otm. 0.000;
ShS4 are external doors right on otm. 0.000.
The "SMD 20P Signal" device relays are used to control the alarm system and send the alarm to the PCP object set, which generates the corresponding control signals in case of fire.
Remote control panels "RTS451KEY" are designed for monitoring and remote testing of linear smoke detectors "6500R." On the front panel of the remote control panel there is a two-color LED indicator of green and red color and a test trigger.
3.2 Fire Warning Organization
Notification of people about the fire at the facility is carried out in the following ways: 1) Voice notification via 5 independent channels (jointly or separately) by broadcasting pre-recorded messages or by broadcasting messages of on-duty personnel through a microphone from a round-the-clock duty post in the temple building. 2) Sound warning by switching on the combined light-and-sound alert at the 24-hour duty station in the temple building. 3) Light warning by turning on "EXIT" wall signs on escape routes from the building.
3.2.1 Description of warning installations
KARAKElectronics equipment - a portable amplifier for 5 zones "TOWER 5200," equipped with an additional module of the CDplayer and radio receiver "KCR1000," is designed to broadcast voice messages and alert in emergency situations; wall speakers with attenuator "KPAWS10" and speakers of column type "KPAC020"; dynamic microphone "D6" with bracket "KMS10D."
The equipment of other companies is a combined lightning sound alert "Lightning-12KP," a light wall indicator ("EXIT") "Lightning." 12
3.2.2 Technical data of warning units
3.2.2.1 Functional parameters of "TOWER 5200" amplifier:
1) Selection of translation zones: 1,2,3,4,5 or all together;
2) Automatic fire warning when connected to the fire alarm panel;
3) Attention signal generator (sirens);
4) 2-band equalizer for each input;
5) Built-in monitoring loudspeaker (1 W);
6) Support of the priority broadcast function;
3.2.2.2 Connection of loudspeakers
The alarm amplifier has an output of 100 V. This system involves the use of a large number of loudspeakers connected to one long loop. Output resistance of amplifier is calculated by formula:
, where 100 V. is the output voltage, 240 W. - output power of amplifier.
The overall loudspeaker line resistance shall not be lower than the amplifier output resistance. If the overall loudspeaker line resistance is lower than the amplifier resistance, this may cause the amplifier to overload and fail.
Wall speakers "KPAWS10" (10 W) due to the presence of an integrated attenuator, allow you to set one of four levels of sound volume; are connected to the line by contacts "COM" (Black) and "500 Ohm" (White).
Wall speakers of column type "KPAC020" (20 W) have input resistance - 500 ohms.
The total resistance of the loudspeaker lines is calculated according to the formula:
The total resistance of the loudspeaker lines for each translation area is:
1 zone (line) "KPAWS10" (2 pcs.) - R = 250 Ohm.;
2 zone (line) "KPAWS10" (2 pcs.) - R = 250 Ohm.;
3 zone (line) "KPAWS10" (3 pcs.) - R = 166.6 Ohm.;
4 zone (line) "KPAWS10" (3 pcs.) - R = 166.6 Ohm.;
5 zone (line) "KPAC020" (2 pcs.) - R = 250 Ohm.;
3.3 Organization of alarm signal transmission to PCP
For transfer of a disturbing signal on PCN LLC ALROSAohrana on an object the following equipment is mounted:
• "Inflow-A-4 (8) 064" instrument;
• "RPDU01" radio transmission device;
• object antenna "AHTOVHF";
• feeder for PPKOP064;
• security detector manual electrical contact point "Astra321";
• "UMB100 HS" radio button.
The specified equipment is installed at the facility in the room of the 24-hour duty station.
3.4 System power supply
According to PUE, fire alarm systems in terms of ensuring the reliability of power supply are classified as electrical receivers of category 1. If there is one power supply source (at objects of category III of reliability of power supply), it is allowed to use electric receivers, storage batteries or uninterrupted power supply units as a backup power source, which must provide power supply to the specified electric receivers in standby mode for 24 hours and in "Alarm" mode for at least 3 hours.
The design envisages installation of "APC BR 1000" uninterruptible power supply at the facility for PC power supply with Orion AWS software, two redundant power supplies "RIP-12" with storage batteries 18 A/h for power supply of fire alarm equipment and one redundant power supply "RIP24" with storage battery of 7 A/h fire alarm system.
Power supply of uninterruptible power supply (UPS) and redundant power supply sources of RIP is provided from distribution power supply network of 220 V, 50 Hz facility.
Protection of electrical circuits of automatic fire extinguishing units and fire alarm system shall be performed in accordance with PUE.
4 Installation of equipment and electrical wiring
The following devices are installed in the room of the 24-hour duty station: PC with AWS Orion software, uninterruptible power supply (UPS) "APC BR 1000," redundant power supply "RIP12" with AKB, redundant power supply "RIP24" with AKB, devices "C2000," "S2000PER 5200,"
In economic. the room in separately locked wall case are established: devices "Signal20P SMD", "S2000PI", "C2000-4-01", the redundant RIP12 power supply with joint stock bank, portable control panels (for "6500R") "RTS451KEY ".
In a dyakonnik the C2000401 device is installed.
Connect fire alarm loops to the instruments by receiving and control firefighters by means of junction boxes and crosses. It is advisable to split fire alarm loops into sections by means of junction boxes.
Lines of SB, RS485 interface, detector control, power supply of detectors, annunciators are made with "twisted pair" cable UTP 2x2x0.53 and UTP 4x2x0.53. Instrument power supply lines, voice warning system lines are made by 2x0.75 VVP wire. Power supply network lines are made by 3x0.75 PVC wire.
Lay the wires: in the premises of the subject paintings - in shtrabs for plaster, in the rest of the rooms - in electrical robe.
5 Equipment grounding
Elements of electrical equipment of the fire alarm and fire warning system must meet the requirements of GOST 12.2.007.0 for the method of protecting a person from electric shock.
Protective grounding (grounding) of the electrical equipment of the fire alarm and fire warning system shall be performed in accordance with the requirements of PUE, SNiP 3.05.06, GOST 12.1.030 and technical documentation of the manufacturer.
6 Requirements for installation and operation
During installation and operation of the plants follow the requirements laid down in the technical documentation of the manufacturers of this equipment, GOST 12.1.019, GOST 12.3.046, GOST 12.2.005.
Проект.dwg
Similar materials
- 09.07.2014
- 01.07.2014
Free downloading for today
Other materials
- 24.01.2023