• RU
  • icon Waiting For Moderation: 4
Menu

Finished goods warehouse of Donskoy - fire fighting

  • Added: 01.07.2014
  • Size: 1 MB
  • Downloads: 1
Find out how to download this material

Description

Plant Warehouse AUPT Design with Explanatory Note, Drawings, Specification

Project's Content

icon
icon Пояснительная записка Склад готорой продукции.doc
icon склад готовой продукции.dwg
icon титульный лист Склад готорой продукции.doc
icon обложка Склад готовой продукции.doc
icon Общие данные Склад готовой продукции.doc

Additional information

Contents

1. General provisions

2. Description and characteristics of the object

3. General Instructions

3.1 Purpose

3.2 Basic Technical Solutions

4. Equipment composition and technical characteristics

4.1 "Signal-20P SMD" safety and fire control device

4.1.1 Purpose

4.2 Control and starting S2000KPB block

4.3 Fire detector IPD - 3.1 M

4.3.1 Purpose

4.3.2 Technical characteristics

4.4 Manual fire detector "SPR-8L"

4.4.1 Purpose

4.4.2 Technical characteristics

4.5 Fire Light Annunciator "Blik-S-24"

4.5.1 Purpose

4.5.2 Technical characteristics

4.6 Thermal detector IP102-2 *

4.7 WFP (H) -4-I-GE-U powder fire extinguishing module

4.8 Sound PKI-2 alert "Oriole"

Appointment

Technical specifications

5. Safety requirements

6. Requirements for performance and organization of works performed by the Customer

7. Change Log Sheet

2. Description and characteristics of the object

The premises in which the automatic fire alarm installation is installed are located at the address: Donskoy, Mkr. Shakhtersky, st. Field, d. 12.

The construction of the walls is brick. Interior decoration: walls - painting with moisture resistant paint; ceiling - whitewash.

The total area of ​ ​ the premises is 1197.3 m 2.

The rooms are equipped with sanitary and electrical communications:

- process pipelines of district heating, hot and cold water, sewage systems;

- telephone lines;

- electric lighting lines.

3. General Instructions

3.1 Purpose

Automatic fire alarm is designed for round-the-clock continuous monitoring of the fire situation, display of the co-standing of the monitored sensors, rooms, information transmission.

Smoke detectors are included in the alarm loop. When the detector is activated, the loop number is indicated. The signal source is determined visually by the LED or remote indication device built into the detector.

3.2 Basic technical solutions.

The "Signal - 20 P SMD" is used as receiving and control equipment in this project.

To detect fires in the early stages, the project provides for the installation of fire smoke detectors "IPD3.1M," heat detectors IP 1022x2. Smoke detectors shall be installed on the ceiling and walls of the premises.

According to NPB 10403, a type II fire warning system has been selected, which includes:

• Sound annunciator "Oriole" with sound pressure of 105 dB.

• Fire lights "BlikS24" installed on escape routes.

• Manual fire detectors "SPR8L" installed on escape routes at a height of 1.5 m from the floor level, according to NPB 882001 *.

The selection of wires and cables, how to lay them for the organization of fire alarm loops and connecting lines was made in accordance with the requirements of PUE, SNiP 3.05.0685, VSN 11687, the requirements of technical documentation for devices and equipment of the fire alarm system. Fire alarm loops shall be made by KSPV wire laid in the conduit. Connection of "SPR8L" manual fire detectors, smoke, heat and fire light detectors "Blik-S-24" shall be made by wire laid in the box.

Power supply of the fire alarm system is carried out according to category 1 according to PUE from the secondary power supply source, which provides power supply to AUPS in the absence of voltage in the network :

a) in standby mode for 24 hours.

b) in "Alarm" mode for at least 3 hours.

Protective grounding (grounding) of electrical equipment of the automatic fire alarm unit shall be performed in accordance with the requirements of PUE, SNiP 3.05.06, GOST 12.1.030 and technical documentation of the manufacturer.

Installation of AUPS systems and EMSS shall be performed in accordance with regulatory documents:

- GOST 12.2.00775 "General Safety Requirements";

- GOST 12.1.01979 "Electrical safety. General requirements and nomenclature of protection types ";

- GOST 12.2.01387 "Manual electrical machines. General safety requirements ";

- OST 4G 0.010.016 "Electrical installation of articles";

- PUE99, PUE-2002, Section 6, 7 "Electrical Installation Rules";

- VSN 37076 "Instructions for installation of wiring in pipes";

- SNiP 3.05.0685 "Electrical devices";

- RD 78.14593 (Part 1, Part 2) "Guidance Document" Security, Fire and Fire Alarm Systems and Complexes. Rules of Work Execution and Acceptance ";

- STM 142994 "Wiring passes through enclosing structures";

- PM 424991 "Systems of automation of technological processes. Installation of grounding networks. "

6. Requirements for production and organization of works,

performed by the Customer

6.1. Installation and commissioning works are carried out taking into account the regulatory and technical documents, which the Customer is obliged to familiarize the Contractor's team with.

6.2. To perform installation and commissioning works, the Customer shall provide the Contractor's team with a closing room for instrument and equipment storage.

6.3. The Customer shall ensure the possibility of unimpeded installation and commissioning works by the Contractor's team in the places specified on the system layout plan, for laying of cable communication lines and installation of equipment during the working day installed at the Customer's enterprise (institution).

6.4. Cable lines of other systems shall not be attached to cable communication lines of the security alarm system.

6.5. By the beginning of commissioning works, the Customer's specialist connects the power supply cable to the power supply source. Power supply of the system must be performed in accordance with the Instructions for designing power supply of industrial enterprises SN 17475 and SNiP 3.05.0685.

6.6. In order to prevent damage to wiring and other communication lines, the Customer shall submit to the head of installation and commissioning works the plan of wiring and other communication lines of the premises in which the cable communication lines of the system should be laid, and ensure the presence of a responsible power engineer for the period of installation works.

6.7. The panel room, where the fire alarm system equipment is located, shall have artificial lighting of at least 150 lux for fluorescent lamps and at least 100 lux for incandescent lamps. Emergency lighting shall provide illumination on working surfaces of at least 10% of the corresponding working lighting standards

Drawings content

icon склад готовой продукции.dwg

склад готовой продукции.dwg

Free downloading for today

Update after: 10 hours 6 minutes
up Up