Closed parking, fire control - electricity
- Added: 30.08.2014
- Size: 423 KB
- Downloads: 1
Description
Project's Content
|
|
АПТ.dwg
|
Пояснит. записка.doc
|
С_О.dwg
|
Спецификация.doc
|
Additional information
Contents
CONTENTS1. GENERAL PART
2. CHARACTERISTICS OF PROTECTED PREMISES
3. PURPOSE AND PRINCIPLE OF OPERATION OF AUTOMATIC POWDER FIRE EXTINGUISHING UNIT
4. PRINCIPLE AND MODES OF OPERATION "GUARANTOR-R"
4.1 "Automatics ON" mode
4.2 "Automatics OFF" mode
4.3 "Diagnostics" mode
5. CALCULATION OF POWDER FIRE EXTINGUISHING PULSE UNIT BY AREA
6. INSTALLATION OF WIRING OF AUTOMATIC POWDER FIRE EXTINGUISHING UNIT
7. EQUIPMENT LOCATION
8. POWER SUPPLY
9. GROUNDING
10. HEALTH AND SAFETY MEASURES
11. PROFESSIONAL AND QUALIFICATION COMPOSITION OF PERSONS WORKING AT THE FACILITY FOR MAINTENANCE AND OPERATION OF AUTOMATIC POWDER FIRE EXTINGUISHING UNIT
12. MAINTENANCE AND MAINTENANCE OF FIRE AUTOMATION UNITS
1. General part
The design of the automatic powder fire extinguishing installation for parking protection is carried out in accordance with the design specification received from the Customer .
The following regulatory documents are used in the development of the project:
NPB 882001 *. Fire fighting and alarm systems. Design Rules and Regulations ;
NPB 11003. List of buildings, structures, premises and equipment to be protected by automatic fire extinguishing and detection units;
NPB 852000 Thermal fire detectors. Fire safety specifications.
SNiP 110195. The instruction about an order of development, coordination, a statement and structure of the project documentation on construction of the enterprises, buildings and constructions;
SNiP 2.08.0289. Public buildings and structures;
SNiP 21.0299. Car parking lots.
GOST 12.3.04691. Fire extinguishing units are automatic. General technical requirements.
PUE-98. Electrical Installation Rules;
Fire safety rules in the Russian Federation. M.: Infram M., 1994;
RD 0090196 Fire Automation Units. Technical Content Rules;
RD 78.14593 Guidelines. Systems and complexes of security, fire and fire alarm. Rules for production and acceptance of works.
Specifications, certificates of conformity and fire safety for the equipment used.
SP 5.13130.2009 automatic fire alarm and fire extinguishing units.
Characteristics of protected premises.
The protected room is an underground parking lot with cars located on it. The total area of the protected room is 662.0 m2. Height of protected rooms - 3.6m.
The project provides for the organization of powder fire extinguishing locally by area on the basis of wireless AUP "GarantR."
Explosion and fire hazard category - B3 (according to NPB 105).
The ventilation is forced, automatically switched off.
Air flow rate is not more than 0.2 m/s, relative humidity is up to 70%. Operating temperature limits from + 5 ° С to + 25 ° С. The walls of the room and floors are reinforced concrete. Dust, vibration, aggressive media and significant electromagnetic interference are absent .
The presence of smoke formations (exhaust gases of vehicles) in the absence of a fire center is possible.
Fire load - centers of fire "B" (flammable and combustible liquids).
In order to increase the level of fire protection of premises and tighten possible foci, manual fire extinguishing means are used.
Composition and purpose of the automatic powder fire extinguishing unit. Technical solutions
Automatic installation of powder fire extinguishing "GarantR" on the basis of powder fire extinguishing modules of WFP type (r) -5-I-GE-UKhL cat.3.1 TU4854002580107302005 ("Garant5") is designed to detect, localize and extinguish fire, in accordance with GOST 12.3.04691 in the protected room and issue of signals to the room with permanent personnel with the presence.
WFP powder fire extinguishing modules (p) -5-I-GE-UKhL cat.3.1 ("Garant7") have fire safety certificate SSPB.RU.OP014.B.00636, compliance certificate No. ROSS RU.H03.H00977.
Wireless automatic fire extinguishing devices "GarantR" have fire safety certificate No. SPB.RU.OP021.B.00553, compliance certificate No. ROSS RU.OS03.H00559.
"Guarantor-R" consists of the following main functional units and devices:
Repeaters:
- "CP" - test panel;
- "RS-K" - relay-coordinator;
"RS-M" - repeater-marshoisator;
Actuators:
"FDR" - control relay unit;
-Development:
- "SCU" - signal processing unit with two spaced-apart units of fire detectors;
Diagnostic Key:
"DB" - diagnostic key.
Fire extinguishing equipment:
powder fire extinguishing modules (type "Garant5").
Based on the characteristics of the room, the type of fire load, the peculiarities of the development of the combustion center in the project, the following technical solutions were made:
To detect the fire, "BOC" signal processing units are adopted, which perform the function of thermal maximum fire detectors, certified according to class A-3 (NPB 852000). At that "SCO" provides two-threshold principle of fire detection from two independent alarm loops, which are an element of SCO design:
- warning "Attention" is generated upon receipt of signal from two temperature sensors on exceeding of the first threshold value of temperature in protected area +64+3˚S;
- "Fire" notification is generated upon receipt of signals from two temperature sensors on exceeding the second threshold temperature value in the same area +763˚S;
2. Signals "Norma," "Attention," "Fire," "Safety" are transmitted through "RSK," "RS-M," "FDR" (relay No. 1,4,5) to control panel "KP" "located on centralized monitoring panel;
3. Setting of "Guarantor" system to "Automatic shut down" and "Start of WFP" mode is performed using "FDR" unit (relays No. 2 and 3) and transmitted to "CP" control panel. A separate FDR generates command pulses for process equipment control.
4. Manual start of Garant-R system is performed by means of "FDR" control relays unit by pressing "WFP Start" button; at the same time, only those fire extinguishing modules will be activated, in which the BOC signal processing units have detected an increase in temperature above + 64 ° С;
5. Information exchange between units of automatic powder fire extinguishing system "GarantR" ("KP," "RSK," "RS-M," "FDR," "BOS," "OBD") is performed via radio channel at frequency 2.4GHz.
6. Programming of GarantR blocks ("RSK", KP, "RSM", "DRILL", "is BAREFOOT") is carried out with the help a brelka of diagnostics of "DB".
Installation of electrical wiring of automatic powder fire extinguishing unit
To execute lines of management of the peripheral equipment of AUPT "GarantR" in parking the GOST 12.2.007.1475, GOST 12176 KPSVVngLS cable 2х2х0.5 - 89 ((Section 3, category C), laid in PVC pipes on the walls and pipes of corrugated PHV (GOST P5082795).
Power supply of "RSK," "RS-M," "FDR" 12V devices must be performed by 2x0.75 ShVP wire in metal box.
Wired power lines of "RSK," "RS-M," "FDR" units of powder fire extinguishing units in protected rooms and along routes shall be laid separately from all power cables, lighting cables and wires in metal box.
In case of parallel open laying, the distance between the wires of the peripheral equipment connecting lines with power and lighting wires must be at least 0.5 m. If it is necessary to lay these wires and cables at a distance of less than 0.5 m from the power and lighting wires, they must have protection against aiming. It is allowed to reduce the distance to 0.25 m from wires and connecting lines without protection from aiming to single lighting wires and control cables.
Equipment placement
Arrangement and installation of "GarantR" APC units shall be carried out in accordance with the design, requirements of NPB 882001 *, Job Instructions and Instructions.
Redundant power supply "RIP12 isp.01" is attached to the wall at the height convenient for maintenance, but not less than 0.8 m from the floor level in the technical room .
The FDR control relay unit is installed on the wall in the technical room at a height of 1.5 m from the floor, RSK and PCM signal repeaters are installed under the ceiling outside the access area, but in the visible control area.
Placement of instruments shall prevent their accidental fall or movement along the installation surface, in which the connected wires and cables may be damaged.
When placing instruments it is necessary to ensure normal illumination of instrument panels.
Placement of "GarantR" automatic control system equipment in cabinets and compartments shielding radio communication is not allowed.
Do not install devices closer than 1 m from heating system components. Measures should be taken to protect devices from direct sunlight.
Power supply
According to PUE, powder fire extinguishing units in terms of ensuring the reliability of power supply are classified as electrical receivers of the 1st category. Therefore, the power supply of the plant must be from one AC source with automatic switching in emergency mode to backup power from batteries.
When the battery is used as a backup power source, the plant shall be operated for at least 24 hours in standby mode and for at least 3 hours in fire mode.
The redundant power supply is "RIP12" is.01 with 17 A/h battery.
Grounding
To ensure the safety of people, all electrical equipment of the Guarantor automatic control system, which has grounding terminals (RIP12 isp.1), must be reliably grounded in accordance with the requirements of the PUE. Installation of grounding devices shall be carried out in accordance with the requirements of "Instructions for implementation of the grounding network in electrical installations" - MN 10276. The resistance of the grounding device used to ground the electrical equipment shall not exceed 4 ohms.
Use the metal frame of the technical room connected to the external grounding electrodes as grounding electrodes. In the circuit of grounding and zero protective conductors there shall be no disconnecting devices and fuses.
Connection of grounding and zero protective conductors to parts of electrical equipment shall be made by welding or bolting.
Professional and qualification composition of persons working at the facility for maintenance and operation of the automatic powder fire extinguishing and fire alarm plant
The personnel number standards take into account the performance of maintenance, and scheduled maintenance of the automatic powder fire extinguishing plant by the enterprise, the organization operating these plants. Maintenance and maintenance works are performed by electromechanics not lower than the fifth discharge.
The number of electromechanics for maintenance and maintenance of the automatic installation of powder fire extinguishing and fire alarm takes into account the necessary time for all components of the installations.
Carrying out the specified types of maintenance and repair works of the designed fire extinguishing plant in order to ensure reliable and trouble-free operation at the facility is carried out by an electrician of the 5th category - 2 people.