Reconstruction of PS 220/35/27.5/10kV. Ventilation

  • Added: 01.07.2014
  • Size: 817 KB
  • Downloads: 1
Find out how to download this material

Description

Calculation of air exchange, form-order, specification, diagrams and axonometries of ventilation system in the building of the common-station control room (including in the battery room).

Project's Content

icon
icon БЗ-3.doc
icon Расчет воздухообмена Б3.doc
icon Специф Б2.doc
icon л.1.dwg
icon л.2.dwg
icon л.3.dwg
icon л.4.dwg
icon л.5.dwg
icon л.6.dwg
icon л.7.dwg
icon л.8.dwg
icon л.9.dwg

Additional information

Calculation of air exchange in battery rooms

1. The purpose of the calculation is to determine the supply air flow to the battery rooms.

Set: - space area - F = 15.7 m2,

- room height H = 4 m,

- number of rooms m = 2 pcs,

- surface area of battery cans electrolyte

in one room Fa = 2.6 m2,

- highest charging current Iz = 143 A,

- number of storage battery elements z = 108 pcs.,

- heat generation in room Q = 0.9 kW,

- maximum ambient air temperature tl = 31.10 С,

- maximum permissible temperature in rooms

storage batteries tdop = 350С.