Individual thermal point 3d
- Added: 24.08.2021
- Size: 13 MB
- Downloads: 2
Description
ITR is located in PNS room. The scheme of connection of the heating system to the heat networks is dependent. The category of heat consumers in terms of reliability of heat supply and heat release is the third.
The ITP design provides for the installation of:
- direct pressure differential regulator Dou15mm, Kvs = 0.25m ³/h ;
- control two-way valve D15, Kvs = 0.25 m ³/h for automatic control of heating system heat flow;
- double circulation pump (1-working, 1-standby) with parameters: G = 0.11 m ³/h, H = 1 m water. on the heating system pipeline jumper;
- instrumentation (see 48/20-AOV).
IT pipelines shall be made of water and gas pipelines as per GOST 3262-75 and electric welded pipelines as per GOST 10704-91.
Drain and air discharge pipelines shall be made of galvanized water and gas pipes as per GOST 3262-75.
Procurement, assembly, testing, adjustment and acceptance of sanitary systems shall be carried out in accordance with SP 1.03.02-2020.
Paint the pipelines of heat supply systems according to GOST 14202-69.