• RU
  • icon Waiting For Moderation: 0
Menu

KOS Automation

  • Added: 02.12.2018
  • Size: 2 MB
  • Downloads: 2
Find out how to download this material

Description

General data Drawings are developed on the basis of:· architectural and construction drawings;· applicable codes and regulations. Automation of general ventilation systems. 1. The control cabinets supplied in package are used to automate the ventilation system. The location of the boards and the cable route are shown in the Equipment and Harness Layout drawing. Cable type, the number of cores is specified in the External Wiring Diagram drawing. 2. The control of the air damper drive and the drive of the three-way valve for regulating the capacity of water heaters is provided. 3. To inform about the air filter clogging, to indicate the differential pressure, a differential pressure sensor-switch is installed on the fan. 4. A channel temperature sensor is installed to monitor the supply air temperature. 5. For electric heaters, overheating protection is provided. 6. The project provided control panels by B3, B4 fans and boards ShchUV1, ShchUV2. The consoles are located in the operator's room. Common Part 1. Cable shall be laid in accordance with PUE. 2. Cable shall be laid in corrugated pipe. Attachment pitch is 0.3m. 3. Cable to control panel in administrative rooms shall be laid in cable-channel. 4. The cable shall be laid on the roof in a galvanized, ultraviolet resistant metal sleeve.

Project's Content

icon 1_proekt-aov_kos.dwg

Additional information

Drawings content

icon 1_proekt-aov_kos.dwg

1_proekt-aov_kos.dwg
up Up